WUI vent requirements in California

What the wildfire building code asks for when you build, add on or replace vents, and what an existing home needs instead.

Which rule is mine?

Listen to this article (about 9 min)

Do you have to change your vents? Only if you build, add on or replace vents in a fire hazard zone the code covers (see below). Then the new vents must be WUI vents: vents that passed ASTM E2886, the lab test for embers and flames [1]. A house with no work going on does not have to change its vents under this code [1][2]. IBHS, the insurance industry's research lab, has its own home standard that some insurers look at. Fine metal mesh counts there [4].

  • WUI Code: the California Wildland-Urban Interface Code. WUI means places where homes meet wildland. It is the state's building code for fire hazard zones, in effect since January 1, 2026 [2].
  • Where it applies: any fire hazard zone in a State Responsibility Area, where CAL FIRE fights wildfires. High and Very High zones in a Local Responsibility Area, where a city, county or local fire district does. And any area a city or county names a WUI area [2].
  • Which version: the code in force on the day you apply for the permit [2].

Which vent rule applies to me?

Start at the top and follow your answers.

Which vent rule applies to my California home?A flowchart. First question: are you building, adding on or replacing vents? If no, nothing is required by the code; for IBHS, use E2886 vents or 1/8 inch metal mesh. If yes, second question: is the home in a zone the code covers, meaning any fire hazard zone in a State area, a High or Very High zone in a local area, or a local WUI area? If yes, the WUI Code applies: vents tested to ASTM E2886, and metal mesh of 1/16 to 1/8 inch on vents on a sloped roof. If no, the regular building code applies, with no WUI vent rule; the IBHS advice still applies. Are you building, adding on or replacing vents? YesNo Is the home in a zone the code covers? Any zone in a State area. High or Very High in a local area. A local WUI area. Nothing required by the code For IBHS: E2886 vents, or metal mesh with openings of 1/8 inch or smaller YesNo WUI Code Vents tested to ASTM E2886 Vents on the roof: metal mesh, 1/16 to 1/8 inch Regular building code No WUI vent rule. The IBHS box still applies.
From the 2025 WUI Code [1][2], and the IBHS Wildfire Prepared Home standard [4]. Not sure of your zone? Check your address.

What counts as a WUI vent?

A vent you buy off the shelf only counts if it passed the ASTM E2886 test. The test has an ember part and a flame part. To pass, three things must hold [1]:

  • No ember fire. Embers that get through do not set the test cotton behind the vent on fire.
  • No flame through. The vent itself does not catch fire when flame hits it.
  • Cool enough behind it. The back of the vent stays under 662°F (350°C).

How to tell: look for "ASTM E2886" on the box, the label or the maker's spec sheet. A plain screen, however fine, does not prove it.

Vents on a sloped roof, such as ridge and dormer vents, are the one exception. They get rust-proof metal mesh that won't burn, with openings from 1/16 to 1/8 inch [1].

Vent by vent

The code covers every opening that lets a house breathe [1]. Exhausts like dryer vents are a gray area. Here is how each kind compares with what IBHS asks of an existing home.

VentWUI Code, new workIBHS, any home
Attic and gable (end wall)E2886 vent. Gable vents at least 10 feet from the property line [1].E2886 vent or 1/8 inch metal mesh [4].
Soffit (under the eaves)E2886 vent [1].E2886 vent or 1/8 inch metal mesh [4].
Crawl spaceE2886 vent, set as close to the ground as practical [1].E2886 vent or 1/8 inch metal mesh. The frame within 6 inches of the ground must not burn [4].
Roof (ridge or dormer)Metal mesh, 1/16 to 1/8 inch [1].E2886 vent or 1/8 inch metal mesh. No spinning turbine vents [4].
DryerNot named in the code text. Ask your building department.A working flap, not mesh [4].

Want to walk your own house first? Our sister site, Home Ready Sonoma, shows how to find and measure every vent.

My house is older. Does a remodel change things?

It can. The code as first printed lets additions and remodels of homes first built before July 1, 2008 skip these rules [1]. A temporary emergency change, in force since January 1, 2026, took that exception out [2]. The same change brought High zones in local areas under the code [2].

So a 1970s house getting a new bedroom in a covered zone now gets WUI vents in the new work. The rest of the house does not have to be brought up to code [2]. Ask at the permit counter whether your vent job needs a permit.

More is coming. In August 2026 the State Fire Marshal brought a permanent version to the state Building Standards Commission. It would also test vents with flame both flat and upright, and say plainly that dryer, kitchen and bath fan exhausts are left out [3]. It is not in force yet.

My city's handout says mesh is fine. Who is right?

Some local handouts list 1/16 to 1/8 inch mesh as a way to meet the code on attic, eave and crawl space vents [6]. The state code is loosely worded. Its mesh rule is written for vents on a sloped roof, such as ridge and dormer vents [1].

Our take: buy vents tested to ASTM E2886. They meet the WUI Code and the IBHS standard, so you do the job once.

No work planned. What about insurance?

The state's Safer from Wildfires list, the steps insurers must give a discount for, includes ember- and fire-resistant vents [5]. For the IBHS Wildfire Prepared Home designation, 1/8 inch metal mesh over the vents you have meets the vent item [4]. Ask your insurer if mesh counts for its discount. Discounts differ by insurer, and we can't promise one. Our sister site Zone Zero Guidelines sets out what each insurance list says about vents.

For how the building code fits with the 100-foot defensible space law and the 5-foot ember-resistant zone (Zone 0), see who enforces which fire rule.

What it means for you

  • Planning a remodel, an addition or new vents? Check your fire hazard zone first. It decides which rule you follow.
  • Shopping for vents? Bring the label or spec sheet showing "ASTM E2886" to your permit counter or contractor.
  • No work planned? Nothing to change under the code. Ask your insurer if 1/8 inch mesh counts, or if it wants tested vents.

Sources

  1. 2025 California Wildland-Urban Interface Code, Chapter 5, sections 503.1 and 504.10 (vents), via GoCodebook (vent test, mesh for vents on a sloped roof, vent locations, the pre-2008 exception as first printed; read November 22, 2026).
  2. 2025 California Wildland-Urban Interface Code, Emergency Supplement, effective January 1, 2026 (PDF, International Code Council) (section 101.3.1 where the code applies, section 101.5 additions, section 503.1 without the pre-2008 exception, history note, permit-date rule; read November 22, 2026).
  3. California Building Standards Commission, Final Express Terms SFM 04/25, Part 7, for the August 25, 2026 meeting (Word file) (proposed vent changes; read November 22, 2026).
  4. IBHS, Wildfire Prepared Home Technical Standard, December 2025 (PDF) (section 2.1.3, vents; read November 22, 2026).
  5. California Department of Insurance, FAQ: Safer from Wildfires Regulation, September 2026 (PDF) (ember- and fire-resistant vents on the discount list; read November 22, 2026).
  6. Los Angeles County Building and Safety, Fire Hazard Severity Zone Standard Construction Notes, 2026 (PDF) (vent notes 8 to 10; read November 22, 2026).

General information, not legal advice or a code ruling for your house. Cities and counties can add stricter rules. Your building department decides what your permit needs.